Specifications - 3000SS
The double check detector assembly consists of two independently operating, spring loaded check valves, two UL/FM, OSY resilient wedge gate valves, and bypass assembly. The bypass assembly consists of a meter (CFM or GPM), a double check including shutoff valves and required test cocks. Each cam-check shall be internally loaded and provide a positive drip tight closure against reverse flow. Cam-check includes a stainless steel cam arm and spring, rubber faced disc and a replaceable seat. The body shall be manufactured from 300 series stainless steel, 100% lead free, through the water way, with a single two-bolt grooved style access cover. No special tools shall be required for servicing. Double Check Detector Assembly shall be an Ames Fire & Waterworks 3000SS series.
|